SANS 1418 · IEC 60502-1 · BS 7870-5

Aerial Bundled Cables (ABC) manufactured in Zambia

Insulated aluminium phase conductors, with or without an aluminium-alloy supporting neutral, XLPE insulated — safe and compact LV overhead distribution for utilities and municipalities.

24standard constructionsSANS 1418main standard0.6/1 kVrated voltage

Aerial Bundled Cables (ABC) — data sheet

SANS 1418 · IEC 60502-1 · BS 7870-5 · 0.6/1 kV · metric units · click a name for the full construction

Data sheet (PDF)
SizePhase conductorsNeutral / messengerOtherApprox.Approx.Max. DC resistance at 20 °CNeutral
CoresAreaStrandingInsul.AreaStrandingMaterialInsul.coresoverall ØweightPhaseNeutralbreak. load
no.mm²no./mmmmmm²no./mmmmno.×mm²mmkg/kmΩ/kmΩ/kmkN
2x10210.67/1.391.20—————12.9982.7146——
2x16216.87/1.751.20—————15.01401.7119——
2x25227.17/2.221.40—————17.52191.0638——
4x16416.87/1.751.20—————18.12811.7119——
1x25+1x54127.17/2.221.4054.57/3.15Al alloy1.60—24.23141.06380.614115.5
3x25+16324.27/2.101.8515.97/1.70Al1.25—24.64071.18881.81432.4
2x50249.57/3.002.00—————25.24080.5826——
4x25427.17/2.221.40—————21.14371.0638——
3x25+54.6327.17/2.221.4054.57/3.15Al alloy1.60—30.55331.06380.614115.5
4x35436.67/2.581.60—————24.65870.7877——
3x25+54+1x25327.17/2.221.4054.57/3.15Al alloy1.601×27.125.66421.06380.614115.5
3x35+54.6336.67/2.581.6054.57/3.15Al alloy1.60—30.26450.78770.614115.5
3x50+25349.57/3.002.0024.27/2.10Al1.85—30.47250.58261.18883.6
4x50451.17/3.051.60—————27.57750.5637——
3x50+54.6351.17/3.051.6054.57/3.15Al alloy1.60—30.57860.56370.614115.5
4x50+2x16451.17/3.051.60————2×16.834.29150.5637——
3x70+54.6374.919/2.241.8054.57/3.15Al alloy1.60—32.61,0390.38500.614115.5
3x70+70374.919/2.241.8070.17/3.57Al alloy1.60—35.71,0880.38500.478019.9
4x70474.919/2.241.80—————35.71,1130.3850——
3x70+54+1x25373.519/2.221.8054.57/3.15Al alloy1.601×27.133.11,1360.39200.614115.5
3x95+50393.319/2.502.3049.57/3.00Al2.00—39.81,2890.30910.58267.3
3x95+70399.319/2.581.8070.17/3.57Al alloy1.60—39.81,3190.29020.478019.9
4x95499.319/2.581.80—————35.91,4200.2902——
3x120+703122.119/2.861.8070.17/3.57Al alloy1.60—43.21,5300.23620.478019.9

Rated strength and DC resistance calculated from the standard construction (Al 1350 61 % IACS, Al alloy 52.5 % IACS, galvanised steel). Weight is approximate. Final values in the order TDS.

Cables are manufactured according to the applicable customer specifications and relevant technical standards. Compliance with specific EN standards is subject to verification and confirmation through the required testing.

Individual ABC cables

Open any size for its cross-section, construction and one-page PDF.

No ABC cable matches your search. Ask us — we manufacture to specification.
Made in Lusaka17,000 m² plant in Lusaka South MFEZ